Damper Close Command [%] | To what percentage do we want to test the closing operation. |
Close Damper Weight [2] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
Damper Open Command [100%] | To what percentage do we want to test the opening operation. |
Open Damper Weight [2] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
Heating Stop Command [%] | To what percentage do we want to test the closing operation. |
Stop Heating Weight [4] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
Pressure Min Threshold [0.4psi] | How much should the duct pressure be minimally. |
Heating AHU - Delta [10△°F] | The threshold tolerance for heating. Delta (DAT VAV - DAT AHU). |
Heating - Delta [5△°F] | The threshold tolerance for heating. Delta between ZT and DAT. |
Max Allowed Flow [30cfm] | Max allowed Flow when fully closed damper. |
Min Flow Indication [100cfm] | Minimum Flow to indicate open damper. |
Relative Flow Tolerance [20%] | How much below the setpoint in % do we allow the flow to be when we have a fully open damper. |
Reaction Time [300sec] | How long to wait for the actuators to fully do their job. |
Stabilization Time [60sec] | How long to wait for the system to come to stability after we have given it an actuator command and the conditions have been fullfiled. |
Measure After [60sec] | How long to wait in seconds to start checking the feedback readings. |
AHU Fan Min Threshold [5%] | How much should the ahu discharge fan be minimally in percentage. |
DAT Heating Threshold [70°F] | How much should the DAT maximally be for our VAV to be able to provide reheat. |
Sec Loop Valve Req [10%] | How much should the Valve minimally be in (%) to run the heating test. |
Heating Start Command [100%] | To what percentage do we want to test the opening operation. |
Start Heating Weight [4] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total.
|