V2 - VAV - Damper Min/Max
This workflow will test a VAV box for its airflow when the damper is at its min and max position.
First, we display the initial conditions of the equipment.
Then we perform precondition checks to ensure the equipment is ready to be tested.
Next we will close the damper.
Finally we will open the damper comparing to max occ cooling flow.
Outcome 🎯 |
This test will check a VAV boxes ability to produce adequate min and max airflow. |
Recommended Schedule 📅 |
Run weekly per floor. Run when there are comfort complaints in a space or floor. Run when new VAV boxes are installed and programmed.
|
Device | Point Requirements 📌 |
VAV | Discharge Airflow |
Damper Command |
Min Occ Cooling Flow |
Max Occ Cooling Flow |
AHU | Discharge Air Pressure |
Preconditions |
1. | AHU Pressure > Min Pressure Threshold |
*Variations
- There is a variant of this workflow that will work without the AHU requirement.
- There is a variant that will work with “floating damper control” I.e. a boolean damper closed command
and boolean damper open command, but in this case we cannot control to a specific close/open percent (i.e. close to 5%, open to 95%).
Workflow Overview
| Test Step | Workflow |
1 | Pre-condition Check | AHU Pressure > Min Pressure Threshold
|
2 | Close Damper | Control: Command Damper Closed Success: Airflow less then % of Max Occ Cooling Flow
|
3 | Open Damper | Control: Command Damper Open Success: Airflow greater than % of Max Occ Cooling Flow
|
Tuning Parameters
| Test Step | Result Description |
1 | AHU Min Pressure | If AHU Pressure is less than this number, the test automatically archives |
2 | Damper Close Command | What % closed do you want to command the damper? |
3 | Close Damper Airflow Threshold | What % of the Max Occ Cooling Flow do you want to set as the airflow threshold when the damper is commanded closed? |
4 | Damper Open Command | What % open do you want to command the damper? |
5 | Open Damper Airflow Threshold | What % of the Max Occ Cooling Flow do you want to set as the airflow threshold when the damper is commanded open? |
6 | Max Sequence Duration | What is the maximum length of time in seconds that a sequence should take to execute? |
7 | Min Sequence Duration | What is the minimum length of time in seconds that a sequence should take to execute? |
8 | Stabilization Time | How long in seconds should the program wait when one sequence finishes, before moving onto the next? |
If you need assistance with interpreting your results, reach out to the support team at [email protected].
Related Articles
VAV - Damper Operation
Testing Procedure Pre-Conditions Check Before testing is started, it must be verified that the VAV is in operation. Verify that VAV is “Occupied”. Verify that it’s parent AHU is “Occupied Verify fan is running by checking that duct pressure is more ...
VAV - Heating Operation
Testing Procedure Pre-Conditions Check Before testing is started, it must be verified that the VAV is in operation. Verify that VAV is “Occupied”. Verify that it’s parent AHU is “Occupied Verify fan is running by checking that duct pressure is more ...
V2 - VAV - Induced Heating
This workflow will test a VAV box for its heating operation. First, we display the initial conditions of the equipment. Then KODE performs precondition checks to ensure the equipment is ready to be tested Next we will lower the setpoint to stop ...
VAV Airflow Setpoint Tracking
This workflow will test a VAV box for its ability to follow the Discharge Airflow Setpoint. First, you will see the equipment’s preconditions. Then, KODE runs a precondition check (verification process) to ensure (confirm) the equipment is ready for ...