| Heating Start Command [100%] | To what percentage do we want to test the opening operation. |
| Start Heating Weight [4] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
| Heating Stop Command [%] | To what percentage do we want to test the closing operation. |
| Stop Heating Weight [1] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
| Stop Cooling Weight [1] | What is the weight on the overall test that we want to assign to this sequence. All sequences will sum up their weights and than each weight will be divided by this total. |
| Cooling Stop Command [%] | To what percentage do we want to test the closing operation. |
| Cooling - Delta [5△°F] | The threshold tolerance for cooling. Delta between ZT and DAT. |
| Fan Max Threshold [5%] | The maximum threshold (%) for a fan off status. |
| Fan Min Threshold [10%] | The minimum threshold (%) for a fan on status.v |
| Reaction Time [240sec] | How long to wait for the actuators to fully do their job. |
| Stabilization Time [60sec] | How long to wait for the system to come to stability after we have given it an actuator command and the conditions have been fullfiled. |
| Measure After [60sec] | How long to wait in seconds to start checking the feedback readings. |
| Heating - Delta [5△°F] | The threshold tolerance for heating. Delta between ZT and DAT. |
| DAT Heating Arb Threshold [28°F] | The DAT above which there would be indication of heating. |
| Fan Current Max Threshold [0.5Amp] | The maximum threshold (Amps) for a fan off status. |
| Fan Current Min Threshold [1Amp] | The minimum threshold (Amps) for a fan on status.
|