Pre-Conditions Check
Before testing is started, it must be verified that the FCU is running.
- Verify that device is “Occupied”.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup Testing Conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.
Stop Active Heating Weight: 1/ 3
- Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active Cooling Weight: 1/ 3
- Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test the Fan
It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.
Test 1: Stop the Fan Weight: 1/ 3
- Command the fan to “OFF”
- Pass if Fan Speed is reports to be less than 5% [Fan Max Threshold]
Test 2: Start the Fan Weight:
- Command the fan to “ON”
- Pass: Fan Percentage >= 10% [Fan Min Threshold]