Chilled Water Diff Pressure Less than Setpoint

☝️ Event: Alerts when chilled water pumps are not able to meet the differential pressure setpoint.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Diff Press - Delta [2△°F]Tolerated Delta from the setpoint.
Relative Water Diff Press - Delta [20%]Tolerated Relative (%) Delta from the setpoint.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.

Chilled Water Temp Greater than Setpoint

☝️ Event: Alerts when the Chilled Water System failed to cool water to its required temperature.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Temp - Delta [2△°F]Tolerated Delta from the setpoint.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.


Chilled/Condenser Water Loop Diff Pressure Less than Setpoint

☝️ Event: Alerts when cooling water pumps are not able to meet the differential pressure setpoint.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Diff Press - Delta [2△°F]Tolerated Delta from the setpoint.
Relative Water Diff Press - Delta [20%]Tolerated Relative (%) Delta from the setpoint.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.

Chilled/Condenser Water Loop Temp Greater than Setpoint

☝️ Event: Alerts when the system failed to cool water to its required temperature.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Diff Press - Delta [2△°F]Tolerated Delta from the setpoint.
Relative Water Diff Press - Delta [20%]Tolerated Relative (%) Delta from the setpoint.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.

Condenser Water Diff Press Less than Setpoint

☝️ Event: Alerts when condenser water pumps are not able to meet the differential pressure setpoint.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Diff Press - Delta [2△°F]Tolerated Delta from the setpoint.
Relative Water Diff Press - Delta [20%]Tolerated Relative (%) Delta from the setpoint.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.

Condenser Water Temp Greater than Setpoint

☝️ Event: Alerts when the system failed to sufficiently cool the condenser water.

Priority
🛑 Critical
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Water Temp - Delta [2△°F]Tolerated Delta from the setpoint.
Pump Min Threshold [5%]The minimum threshold (%) for a pump on status.
Pump Current Min Threshold [1Amp]The minimum threshold (Amps) for a pump on status.
    • Related Articles

    • Hot Water System Faults

      Hot Water Diff Pressure Less than Setpoint ☝️ Event: Alerts when hot water pumps are not able to meet the differential pressure setpoint. Priority ? Critical Domain ? Heating Operation Failure Tuning Parameters Display Hint Alarm On Delay [15min] ...
    • Airside Faults

      CO2 Near Max Setpoint ☝️ Creates an Event when CO2 concentration is greater than acceptable levels while occupied Priority ? Alert Domain ? Air Quality Tuning Parameters Display Hint Alarm On Delay [15min] Delay in minutes after alarm conditions ...
    • FDD on Mobile App

      Introduction Fault Detection and Diagnostics (FDD) is a proactive approach for identifying and analyzing system failures or faults within a building's infrastructure at their earliest stages. Navigate through FDD Log into the Mobile App and you’ll ...
    • Routines Page

      KODE gives you a pre-configured library of FDD Routines that you can use to configure your own systems more quickly and easily eliminates the need to create new routines from scratch. To meet your use cases, the FDD Routines page allows you to view ...
    • FDD Batch Configuration

      The goal of FDD configuration is to establish monitoring and alarms on any of the integrated pieces of equipment to determine a system fault. Follow the below steps to configure FDDs of your choice. Go to KDOE OS and select a site. Navigate to the ...