Airside Faults

Airside Faults

CO2 Near Max Setpoint

☝️ Creates an Event when CO2 concentration is greater than acceptable levels while occupied
Priority
🔔 Alert
Domain
🍃 Air Quality
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
CO2 Max Arbitrary Threshold [800ppm]When no setpoint in place, when would we like to be notified for breach of CO2 regualtions
Relative Setpoint Deadband [10%]How much do we tolerate difference from the setpoint in % for CO2.
Setpoint Deadband [50ppm]How much do we tolerate difference from the setpoint for CO2. Suggest this to be a minimal value.


Cooling Fully Open for Long Periods

☝️ Creates an Event when unit is commanded to maximum cooling for too long
Priority🔔  Alert
Domain❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.

Cooling Off in Cooling Mode

☝️ Alerts when zone temperature is high and cooling is not active.
Priority
🔔 Alert
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.

Cooling Off in Cooling Mode w/ Discharge Temperature

☝️ Alerts when zone temperature is high and cooling is not active.

Priority
 ⚠️ Warning
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.


Cooling Off in Cooling Mode w/ Discharge Temperature

☝️ Alerts when zone temperature is high and cooling is not active
Priority⚠️ Warning
Domain❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.


Cooling Stuck Open

☝️ Alerts when zone temperature is high and cooling is not active.

Priority
 ⚠️ Warning
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(ZT SPT, ZT) - Delta [1△°F]Delta between after which we want the operation to be off for sure.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Damper Fully Open for Long Periods

☝️ Alerts when damper is at its maximum position for too long.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.


Damper Operation Failure

☝️ Alerts when discharge airflow is less than setpoint and damper is greater than its minimum position.

Priority
🔔 Alert
Domain
🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Damper Operation Failure in Cooling Mode

☝️ Alerts when the damper fails to open when heating is required.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Damper Operation Failure in Heating Mode

☝️ Alerts when the damper fails to open when heating is required.

Priority
 ⚠️ Warning
Domain
🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Discharge Fan Operation Failure

☝️ Alerts when the discharge fan is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Discharge Temperature Greater than Setpoint while Occupied

☝️ Alerts when discharge temperature is too high while in cooling mode and occupied.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Power Min Threshold [1W or kW]The minimum threshold (w/kws) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Duct Pressure Less Than Setpoint while Fan Near Maximum

☝️ Alerts when fan is running at its upper limit and does not meet discharge pressure setpoint.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Pressure Tolerance [20%]How much (%) below/above Setpoint, do we tolerate Pressure to be.
Nominal Pressure Tolerance [0.1psi]How much below/above Setpoint, do we tolerate Pressure to be. This should generally be a low number.
Fan Min Position [95%]Fan Minimal Position (%) when experiencing Pressure Issues.


Fan Operation Failure while Duct Pressure Less than Setpoint

☝️ Alerts when fan is running at its lower limit and does not meet discharge pressure setpoint.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Nominal Pressure Tolerance [0.1psi]How much below/above Setpoint, do we tolerate Pressure to be. This should generally be a low number.
Relative Pressure Tolerance [20%]How much (%) below/above Setpoint, do we tolerate Pressure to be.
Fan Min Position [95%]Fan Minimal Position (%) when experiencing Pressure Issues.


Fan/Pump Operation Failure

☝️ Alerts when unit is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.


Flow Less Than Setpoint
☝️ Alerts when discharge airflow is less than setpoint and damper is at or less than its minimum position.

Priority
 🔔 Alert
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Flow Less Than Setpoint in Cooling Mode
☝️ Alerts when damper fails to reach flow setpoint when in cooling mode.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Flow Less Than Setpoint in Heating Mode
☝️ Alerts when damper fails to reach flow setpoint when in heating mode.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Heating Fully Open for Long Periods
☝️ Alerts when unit is outputting maximum cooling for too long.

Priority
 🔔 Alert
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.



Heating Off in Heating Mode
☝️ Alerts when zone temperature is too low and heating is not active.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.


Heating Off in Heating Mode w/ Discharge Temperature
☝️ Alerts when discharge temperature is too low and heating is not active.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.


Heating Stuck Open
☝️ Alerts when there is a heating source detected while in cooling mode.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(ZT SPT, ZT) - Delta [1△°F]Delta between after which we want the operation to be off for sure.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Cooling Operation
☝️ Alerts when the unit is actively cooling, but there isn’t a sufficient drop in zone temperature.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.
Cooling Valve Min Position [90%]When in Cooling Mode, what is the minimum actuator position to make the check for insufficiency.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Cooling Operation w/ Discharge Temperature & Setpt
☝️ Alerts when the unit is actively cooling, but there isn’t a sufficient drop in discharge temperature.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.
Cooling Valve Min Position [90%]When in Cooling Mode, what is the minimum actuator position to make the check for insufficiency.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Heating Operation
☝️ Alerts when the unit is actively heating, but there isn’t a sufficient rise in zone temperature.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
Heating Valve Min Position [90%]Minimal Position to indicate (near) full capacity operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.


Insufficient Heating Operation w/ Discharge Temperature & Setpt
☝️ Alerts when the unit is actively heating, but there isn’t a sufficient rise in discharge temperature.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
Heating Valve Min Position [90%]Minimal Position to indicate (near) full capacity operation.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Return Fan Operation Failure
☝️ Alerts when the return fan is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.


Temperature Greater than Setpoint while Occupied
☝️ Alerts when zone temperature is outside the acceptable range while in cooling mode and occupied..

Priority
 🔔 Alert
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Arbitrary Heating Setpoint [66°F]When a device doesn't have setpoint, what is the arbitrary setpoint below which you would like to get notified.
Aribitrary Cooling Setpoint [75°F]When a device doesn't have setpoint, what is the arbitrary setpoint above which you would like to get notified.


Temperature Less than Setpoint while Occupied
☝️ Alerts when zone temperature is outside the acceptable range while in heating mode and occupied.

Priority
 🔔 Alert
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Arbitrary Heating Setpoint [66°F]When a device doesn't have setpoint, what is the arbitrary setpoint below which you would like to get notified.
Aribitrary Cooling Setpoint [75°F]When a device doesn't have setpoint, what is the arbitrary setpoint above which you would like to get notified.



    • Related Articles

    • Routines Page

      KODE gives you a pre-configured library of FDD Routines that you can use to configure your own systems more quickly and easily eliminates the need to create new routines from scratch. To meet your use cases, the FDD Routines page allows you to view ...
    • Chilled Water System Faults

      Chilled Water Diff Pressure Less than Setpoint ☝️ Event: Alerts when chilled water pumps are not able to meet the differential pressure setpoint. Priority ? Critical Domain ❄️ Cooling Operation Failure Tuning Parameters Display Hint Alarm On Delay ...
    • Hot Water System Faults

      Hot Water Diff Pressure Less than Setpoint ☝️ Event: Alerts when hot water pumps are not able to meet the differential pressure setpoint. Priority ? Critical Domain ? Heating Operation Failure Tuning Parameters Display Hint Alarm On Delay [15min] ...
    • FDD - Faut Detection and Diagnostics

      Introduction Fault Detection and Diagnostics (FDD) is a proactive approach for identifying and analyzing system failures or faults within a building's infrastructure at their earliest stages. Navigate through FDD Log into the Mobile App and you’ll ...
    • FDD Batch Configuration

      The goal of FDD configuration is to establish monitoring and alarms on any of the integrated pieces of equipment to determine a system fault. Follow the below steps to configure FDDs of your choice. Go to KDOE OS and select a site. Navigate to the ...