Airside Faults

Airside Faults

CO2 Near Max Setpoint

☝️ Creates an Event when CO2 concentration is greater than acceptable levels while occupied
Priority
🔔 Alert
Domain
🍃 Air Quality
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
CO2 Max Arbitrary Threshold [800ppm]When no setpoint in place, when would we like to be notified for breach of CO2 regualtions
Relative Setpoint Deadband [10%]How much do we tolerate difference from the setpoint in % for CO2.
Setpoint Deadband [50ppm]How much do we tolerate difference from the setpoint for CO2. Suggest this to be a minimal value.


Cooling Fully Open for Long Periods

☝️ Creates an Event when unit is commanded to maximum cooling for too long
Priority
🔔  Alert
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.

Cooling Off in Cooling Mode

☝️ Alerts when zone temperature is high and cooling is not active.
Priority
🔔 Alert
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.

Cooling Off in Cooling Mode w/ Discharge Temperature

☝️ Alerts when zone temperature is high and cooling is not active.

Priority
 ⚠️ Warning
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.


Cooling Off in Cooling Mode w/ Discharge Temperature

☝️ Alerts when zone temperature is high and cooling is not active
Priority
⚠️ Warning
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Valve Min Position [5%]Minimal Position to indicate (near) full capacity operation.


Cooling Stuck Open

☝️ Alerts when zone temperature is high and cooling is not active.

Priority
 ⚠️ Warning
Domain
❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(ZT SPT, ZT) - Delta [1△°F]Delta between after which we want the operation to be off for sure.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Damper Fully Open for Long Periods

☝️ Alerts when damper is at its maximum position for too long.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.


Damper Operation Failure

☝️ Alerts when discharge airflow is less than setpoint and damper is greater than its minimum position.

Priority
🔔 Alert
Domain
🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Damper Operation Failure in Cooling Mode

☝️ Alerts when the damper fails to open when heating is required.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Damper Operation Failure in Heating Mode

☝️ Alerts when the damper fails to open when heating is required.

Priority
 ⚠️ Warning
Domain
🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Discharge Fan Operation Failure

☝️ Alerts when the discharge fan is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Discharge Temperature Greater than Setpoint while Occupied

☝️ Alerts when discharge temperature is too high while in cooling mode and occupied.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Power Min Threshold [1W or kW]The minimum threshold (w/kws) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Duct Pressure Less Than Setpoint while Fan Near Maximum

☝️ Alerts when fan is running at its upper limit and does not meet discharge pressure setpoint.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Pressure Tolerance [20%]How much (%) below/above Setpoint, do we tolerate Pressure to be.
Nominal Pressure Tolerance [0.1psi]How much below/above Setpoint, do we tolerate Pressure to be. This should generally be a low number.
Fan Min Position [95%]Fan Minimal Position (%) when experiencing Pressure Issues.


Fan Operation Failure while Duct Pressure Less than Setpoint

☝️ Alerts when fan is running at its lower limit and does not meet discharge pressure setpoint.

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Nominal Pressure Tolerance [0.1psi]How much below/above Setpoint, do we tolerate Pressure to be. This should generally be a low number.
Relative Pressure Tolerance [20%]How much (%) below/above Setpoint, do we tolerate Pressure to be.
Fan Min Position [95%]Fan Minimal Position (%) when experiencing Pressure Issues.


Fan/Pump Operation Failure

☝️ Alerts when unit is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.


Flow Less Than Setpoint
☝️ Alerts when discharge airflow is less than setpoint and damper is at or less than its minimum position.

Priority
 🔔 Alert
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Flow Less Than Setpoint in Cooling Mode
☝️ Alerts when damper fails to reach flow setpoint when in cooling mode.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Flow Less Than Setpoint in Heating Mode
☝️ Alerts when damper fails to reach flow setpoint when in heating mode.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Relative Flow Tolerance [10%]How much (%) below/above Setpoint, do we tolerate Flow to be.
Nominal Flow Tolerance [20cfm]How much below/above Setpoint, do we tolerate Flow to be. This should generally be a low number.
Damper Min Position [95%]Damper Minimal Position to indicate a starved box.


Heating Fully Open for Long Periods
☝️ Alerts when unit is outputting maximum cooling for too long.

Priority
 🔔 Alert
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Alarm Delay [60min]Delay in minutes after alarm conditions fulfilled to start the alarm.



Heating Off in Heating Mode
☝️ Alerts when zone temperature is too low and heating is not active.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.


Heating Off in Heating Mode w/ Discharge Temperature
☝️ Alerts when discharge temperature is too low and heating is not active.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.


Heating Stuck Open
☝️ Alerts when there is a heating source detected while in cooling mode.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(ZT SPT, ZT) - Delta [1△°F]Delta between after which we want the operation to be off for sure.
Heating Valve Min Position [10%]When in Heating Mode, what is the minimum actuator position we want.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Cooling Operation
☝️ Alerts when the unit is actively cooling, but there isn’t a sufficient drop in zone temperature.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.
Cooling Valve Min Position [90%]When in Cooling Mode, what is the minimum actuator position to make the check for insufficiency.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Cooling Operation w/ Discharge Temperature & Setpt
☝️ Alerts when the unit is actively cooling, but there isn’t a sufficient drop in discharge temperature.

Priority
 ⚠️ Warning
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.
Cooling Valve Min Position [90%]When in Cooling Mode, what is the minimum actuator position to make the check for insufficiency.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Insufficient Heating Operation
☝️ Alerts when the unit is actively heating, but there isn’t a sufficient rise in zone temperature.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
Heating Valve Min Position [90%]Minimal Position to indicate (near) full capacity operation.
(DAT VAV, DAT AHU) - Delta [3△°F]Delta between DAT VAV and DAT AHU for sufficient Heating Operation.


Insufficient Heating Operation w/ Discharge Temperature & Setpt
☝️ Alerts when the unit is actively heating, but there isn’t a sufficient rise in discharge temperature.

Priority
 ⚠️ Warning
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
(DAT VAV, ZT) - Delta [5△°F]Delta between DAT VAV and ZT for sufficient Heating Operation.
Heating Valve Min Position [90%]Minimal Position to indicate (near) full capacity operation.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.


Return Fan Operation Failure
☝️ Alerts when the return fan is not operating as commanded (feedback does not match command).

Priority
 ⚠️ Warning
Domain
 🌀 AHU Fan / Pressure Issue
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Fan Current Min Threshold [1Amp]The minimum threshold (Amps) for a fan on status.
Fan Max Threshold [2%]The maximum threshold (%) for a fan off status.
Fan Current Max Threshold [0.1Amp]The maximum threshold (Amps) for a fan off status.
Fan Min Threshold [5%]The minimum threshold (%) for a fan on status.


Temperature Greater than Setpoint while Occupied
☝️ Alerts when zone temperature is outside the acceptable range while in cooling mode and occupied..

Priority
 🔔 Alert
Domain
 ❄️ Cooling Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Arbitrary Heating Setpoint [66°F]When a device doesn't have setpoint, what is the arbitrary setpoint below which you would like to get notified.
Aribitrary Cooling Setpoint [75°F]When a device doesn't have setpoint, what is the arbitrary setpoint above which you would like to get notified.


Temperature Less than Setpoint while Occupied
☝️ Alerts when zone temperature is outside the acceptable range while in heating mode and occupied.

Priority
 🔔 Alert
Domain
 🔥 Heating Operation Failure
Tuning Parameters
DisplayHint
Alarm On Delay [15min]Delay in minutes after alarm conditions fulfilled to start the alarm.
Start Delay [30min]Delay in minutes after the equipment starts working to check for the alarm conditions.
Heating Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Cooling Setpoint Deadband [1.5△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Single Setpoint Deadband [3△°F]When a single setpoint in place, what is the tolerated difference from the setpoint.
Return to Normal Delay [5min]Delay in minutes after alarm conditions fulfilled to stop the alarm.
Arbitrary Heating Setpoint [66°F]When a device doesn't have setpoint, what is the arbitrary setpoint below which you would like to get notified.
Aribitrary Cooling Setpoint [75°F]When a device doesn't have setpoint, what is the arbitrary setpoint above which you would like to get notified.



    • Related Articles

    • FDD Dashboard

      Fault Detection and Diagnostics (FDD) is a proactive process that identifies and analyzes system failures or faults within a building's infrastructure at their earliest stages. By detecting these faults early on, FDD enhances system performance, ...
    • Hot Water System Faults

      Hot Water Diff Pressure Less than Setpoint ☝️ Event: Alerts when hot water pumps are not able to meet the differential pressure setpoint. Priority ? Critical Domain ? Heating Operation Failure Tuning Parameters Display Hint Alarm On Delay [15min] ...
    • Chilled Water System Faults

      Chilled Water Diff Pressure Less than Setpoint ☝️ Event: Alerts when chilled water pumps are not able to meet the differential pressure setpoint. Priority ? Critical Domain ❄️ Cooling Operation Failure Tuning Parameters Display Hint Alarm On Delay ...
    • What is FDD?

      Understanding Fault Detection & Diagnostics What is a Fault? A fault is a period of time in which a specified condition is true on a specific device. For example, this is a fault: @8:00am AHU-1 Could not maintain discharge temperature within setpoint ...
    • Event Library

      KODE OS automatically monitors the operation of your equipment and will raise a user’s awareness whenever event threshold conditions are met. Out of the box, KODE OS supports an event library that can be deployed to monitor HVAC, Fire, ...