Pressure Min Threshold [0.4psi] | How much should the duct pressure be minimally. |
RAT Cooling Threshold [60°F] | How much should the RAT minimally be for our loop to be able to provide cooling. |
Loop Diff Pressure Min Threshold [3△°F] | How much should the loopsystem differential pressure be minimally. |
Ventilation - Delta [5△°F] | The temperature threshold tolerance for fully open mixed damper. Delta below RAT for fully open mixed damper. |
Cooling - Delta [10△°F] | The threshold tolerance for cooling. Delta between MAT and DAT. |
Heating - Delta [10△°F] | The threshold tolerance for heating. The threshold tolerance for cooling. Delta between MAT and DAT. |
DAT Arb Cooling Threshold [45°F] | The DAT below which there would be indication of cooling. |
Reaction Time [300sec] | How long to wait for the actuators to fully do their job. |
Stabilization Time [60sec] | How long to wait for the system to come to stability after we have given it an actuator command and the conditions have been fullfiled. |
Measure After [60sec] | How long to wait in seconds to start checking the feedback readings. |